The following is a list of the factory default settings for the WattNode BACnet meter. These settings are grouped under the BACnet AnalogValue, BinaryValue and MultiStateValue type objects and may be customized for a particular application by using the BACnet WriteProperty or WritePropertyMultiple service to write to the PresentValue property of each object. These settings are described in the WattNode BACnet Manual and summarized in the WattNode BACnet Objects Spreadsheet.

AnalogValue Settings

  • ConfigPasscode – 0 (no passcode is assigned and the passcode protected settings may be freely changed)
  • CtAmpsA – 5 amperes
  • CtAmpsB – 5 amperes
  • CtAmpsC – 5 amperes
  • DemPerMins – 15 minutes
  • DemSubints – 1 subinterval
  • GainAdjustA – 10000 (this results in a gain factor of one, since the gain = GainAdjustA / 10000)
  • GainAdjustB – 10000 (this results in a gain factor of one, since the gain = GainAdjustB / 10000)
  • GainAdjustC – 10000 (this results in a gain factor of one, since the gain = GainAdjustC / 10000)
  • PhaseAdjustA – 0 millidegrees
  • PhaseAdjustB – 0 millidegrees
  • PhaseAdjustC – 0 millidegrees
  • CreepLimit – 1500 (this results in a creep limit of 1/1500th of full-scale power, since the limit = 1 / CreepLimit)
  • PtRatio – 1 (this results in a voltage scale factor of one, which is appropriate when a potential transformer is not used)

BinaryValue Settings

  • InvertCtA – 0 (not inverted)
  • InvertCtB – 0 (not inverted)
  • InvertCtC – 0 (not inverted)

MultiStateValue Settings

  • PhaseOffset – 4 (three-phase balanced)
  • Averaging – 1 (fast)