This page documents the UL (Underwriters Laboratories) conditions of acceptability for the Accu-CT® family of current transformers, ACTL-0750 and ACTL-1250 series. The conditions of acceptability are not generally needed when using the Accu-CT with a WattNode meter, but if you are using it in other applications or seeking approval to use it with other devices, these may be needed.

UL FILE

E363660

PRODUCT COVERED

Energy-monitoring Current Transformers, Series ACTL-0750 and ACTL-1250 series may be followed by numbers followed by dash, may be followed by characters.

Energy-monitoring Current Transformers Certified for Canada, Series ACTL-0750 and ACTL-1250 series may be followed by numbers followed by dash, may be followed by characters.

GENERAL

These devices are single-phase open type air cooled encapsulated current transformers. They may be provided with a burden resistor that enables AC voltage secondary output.

They are suitable for use in 55°C ambient in accordance with the requirements of IEEE Standard C57.13-1993 and CAN/CSA 60044-1.

CONDITIONS OF ACCEPTABILITY

  1. The transformers shall be installed within equipment that will provide an acceptable enclosure.
  2. The suitability of the lead wires shall be determined in the end use product.
  3. These transformers have not been tested for accuracy, impulse and mechanical tests, only temperature and dielectric voltage-withstand tests were performed.
  4. The acceptability of the mounting means for these transformers shall be judged in the end use.