WattNode® LonWorks® – Downloads
These downloads apply to the following two families of WattNode meters for the LonTalk protocol:
- WattNode LonWorks
- WattNode Revenue for LonWorks
- WattNode Logger for LonWorks
Sales Brochure
- WattNode Plus Brochure (PDF, 2 pages)
- WattNode Logger Brochure (PDF, 2 pages)
- WattNode Revenue Brochure (PDF, 1 page)
Manuals, Technical Documents, and XIF File
Short and long versions of manuals are available and apply to both the WattNode Plus for LonWorks and WattNode Revenue for LonWorks models.
Installation Guide The following short installation guide applies for all LonWorks models and options and is intended for the electrician or electrical installer, as well as anyone doing network wiring.
- Installation Guide (PDF, 16 pages)
Reference Manuals These are the long (40-50 page) manuals that provide detailed installation, operation, and reference information for the different WattNode for LonWorks meters.
WattNode Plus for LonWorks
- Reference Manual (PDF, 43 pages)
WattNode Logger for LonWorks
- Reference Manual (PDF, 45 pages)
WattNode Plus for LonWorks – Option B
- Reference Manual (PDF, 36 pages)
Manual Supplements
- MS-20 WattNode for LonWorks – Option PT (PDF, 8 pages) – Manual supplement for Option PT with potential transformers.
- MS-22 WattNode for LonWorks – FRAM Firmware Update (PDF, 2 pages) – Manual supplement with information on a firmware update to improve non-volatile memory reliability.
- MS-25 WattNode for LonWorks – Invert CT Polarity (PDF, 2 pages) – Manual supplement with information on the invert CT feature.
- Engineering Specifications (DOC, 1 page))
Description
The WattNode® meter for LonWorks is a kilowatt-hour (kWh) energy and power (kW demand) meter that communicates on a LonWorks® network and measures 1, 2, or 3 phases with voltages from 120 to 600 Vac and currents from 5 to 6,000 amps in delta (line-to-line) and wye (line-to-neutral) configurations. For built-in data logging, see the WattNode Logger for LonWorks.
Measurements
- Net Real Energy: kilowatt-hours (phase A, B, C, sum of all phases)
- Positive Real Energy: kilowatt-hours (phase A, B, C, sum of all phases)
- Bidirectional Real Power: Watts (phase A, B, C, and sum of all phases)
- Reactive Power: VARs (phase A, B, C, and sum of all phases)
- Power Factor: PF (phase A, B, C, all phases)
- Reactive Energy: kVAR-hours (sum of all phases)
- AC Frequency
- RMS Voltage: (phase to neutral A, B, C)
- Computed RMS Current: (phase A, B, C)
- Demand kW
- Peak Demand kW
WattNode Plus—Features
WNC FT10 | WNC FT10-L | RWNC FT10 | Features |
---|---|---|---|
Meets the accuracy requirements of the ANSI C12.1 standard | |||
Data Logging model –L. See the Option Tab. | |||
Supports LonWorks TP/FT-10 twisted-pair free topology network using Echelon’s® LonTalk® (ANSI/CEA-709.1-B-2002) network protocol. | |||
LonMark® 3.4 Certified | |||
Small form factor for easy installation inside most electrical panels, see a example WattNode for LonWorks Installation Example. | |||
Pluggable screw terminals for easy wiring | |||
Nominal accuracy 0.5%—See the Reference Manual (PDF, 43 pages) for details | |||
True RMS power even with leading or lagging power factor and chopped or distorted waveforms | |||
Measure variable speed motor drives used in HVAC, refrigeration, and pumping systems | |||
Safe CT’s (Current Transformers), output 0.333 Vac at rated current. |
|||
Assembled in USA, qualified under the Buy American provision in the American Recovery and Reinvestment Act of 2009 (ARRA). | |||
Five year warranty |
WattNode for LonWorks—Specifications
These specifications apply to the following families of WattNode® meters with the LonTalk® protocol:
- WattNode Plus
- WattNode Plus Revenue
Electrical
- Line powered
- Operating Voltage Range: –20% to +15% of the nominal rated voltage
- Power Line Frequency: 50 or 60 Hz
- CT Input: 0.333 Vac nominal, 0 to 0.5 Vac operating, 3 Vac maximum
Measurement Configurations
- Single phase: two or three wire
- Three phase, four wire wye
- Three phase: three wire delta
- Three phase: four wire delta
Communication
- Protocol: Echelons® LonTalk® (ANSI/CEA-709.1-B-2002, EN 14908, GB/Z 20177.1-2006)
- Transceiver: Echelon TP/FT-10
- Bit Rate: 78 kbps
- Maximum Nodes: 64 per subnet
- Maximum Distance:
- Free Topology: 500 meters
- Bus Topology: 2700 meters
- Maximum Stub Length:
- Free Topology: Unlimited
- Bus Topology: 3 meters
Accuracy
WattNode Plus for LonWorks
- 0.5% nominal (see manuals for details)
WattNode Logger for LonWorks
- 0.5% nominal (see manuals for details)
- Clock accuracy: ± 2 minutes per year (battery backed)
WattNode Revenue for LonWorks
- 0.5% nominal (see manual for details)
- Meets accuracy requirements of the ANSI C12.1 standard when used with CCS CTs rated for IEEE C57.13 class 0.6 accuracy (see Revenue Grade CTs).
Data Logging Model –L
This model is only available on standard model WattNode for LonWorks. The data logging model is for special applications where the LonTalk network is not available or not reliable. Order the logging model by adding a –L to the end of the part number. For example: WNC-3Y-208-FT10-L.
The data logging model provides internal logging to non-volatile memory. Logging intervals can be selected from 1 minute to 12 hours. Memory allows logging of up to 250 days of 15-minute data. The logged values are:
- Date and Time
- Net Energy (A, B, C and Sum)
- Reactive Energy (Sum)
- Positive Energy (Sum)
- Real and Reactive Power (A, B, C and Sum)
- Voltage, Current and Power Factor (A, B, C)
- Demand
Regulatory
- FCC Class B, EN 55022 Class B
- UL and cUL Listed (UL 61010-1), file number E312220
- CE Mark and RoHS Declaration of Conformity
- Immunity: EN 61326: 2002 (Industrial Locations)
Environmental
- Operating Temperature: –30° to 55°C
- Humidity: Up to 90% RH (non-condensing)
Mechanical
Case Dimensions (Click on the image for a larger view.)
- Enclosure:High impact, ABS plastic
- High impact, ABS plastic
- Flame Resistance Rating: 94V-0, IEC FV-0
- Size: 6.1 × 3.35 × 1.5 in. (155 × 85 × 38.1 mm)
- Weight: 10.4 oz (295 g)
- Connectors: Euroblock style pluggable screw terminal blocks
- Green: 22 to 12 AWG (0.32 to 2.5 mm2), 600 V
- Black: 22 to 12 AWG (0.32 to 2.5 mm2), 300 V
- Screw torque 4.4 lbf·in (0.5 N·m)
WattNode® Plus for LonWorks® – Model Part Numbers
Standard Model | Logger Model | Revenue Model | Vac Line to Neutral | Vac Line to Line | Electrical Service Types | Neutral Required |
---|---|---|---|---|---|---|
WNC-3Y-208-FT10
|
WNC-3Y-208-FT10-L
|
RWNC-3Y-208-FT10
|
120 | 208-240 | Single-Phase 120V with neutral Single-Phase 3-Wire 120/240V 3-Phase 4-Wire Wye 120/208V | Yes |
WNC-3Y-400-FT10
|
WNC-3Y-400-FT10-L
|
RWNC-3Y-400-FT10
|
230 | 400 | Single-Phase 230V with neutral 3-Phase 4-Wire Wye 230/400V | Yes |
WNC-3Y-480-FT10
|
WNC-3Y-480-FT10-L
|
RWNC-3Y-480-FT10
|
277 | 480 | Single-Phase 277V with neutral 3-Phase 4-Wire Wye 277/480V | Yes |
WNC-3Y-600-FT10
|
WNC-3Y-600-FT10-L
|
RWNC-3Y-600-FT10
|
347 | 600 | Single-Phase 347V with neutral 3-Phase 4-Wire Wye 347/600V | Yes |
WNC-3D-240-FT10
|
WNC-3D-240-FT10-L
|
RWNC-3D-240-FT10
|
See below | 208-240 | Single-Phase 208V (No neutral) Single-Phase 240V (No neutral) Single-Phase 3-Wire 120/240V 3-Phase 3-Wire Delta 208V–240V (No neutral) 3-Phase 4-Wire Wye 120/208V | |
WNC-3D-400-FT10
|
WNC-3D-400-FT10-L
|
RWNC-3D-400-FT10
|
See below | 400 | 3-Phase 3-Wire Delta 400V (No neutral) 3-Phase 4-Wire Wye 230/400V | |
WNC-3D-480-FT10
|
WNC-3D-480-FT10-L
|
RWNC-3D-480-FT10
|
See below | 480 | 3-Phase 3-Wire Delta 480V (No neutral) 3-Phase 4-Wire Wye 277/480V |
- Voltage Ranges listed in table are -20% to +15% of nominal. For 3D-240 models, this is -20% of 208 Vac (166 Vac) to +15% of 240 Vac (276 Vac). Operating Frequencies: 50/60 Hz
- Delta models (3D in part number) work either with or without a neutral connection, but require a line-to-line voltage connection for operating power.
Network Services Support
- WattNode for LonWorks External Interface Files (xif)
- LonWorks Resource Files
- LNS Plug-in for WattNode – Article with downloads
Firmware Upgrade
- WattNode for LonWorks Versions
- Current Versions:
- WattNode Plus and Revenue: WattNode for LonWorks – Firmware Version 3.39
- WattNode Logger Option L: WattNode for LonWorks – Firmware Version 3.69
Option Specific Downloads
WattNode Plus Only
Option B – Emulates the legacy WNB-xx-xxx-FT10 series of WattNode meters
See WattNode for LonWorks – Option B for downloads.
WattNode Plus and WattNode Logger Only
Option PT – Allows monitoring higher voltage services.
See WattNode LonWorks – Option PT for downloads.
WattNode® for LonWorks® – Options
Option CT
This option configures the network variable nciCtAmps to the specified CT rated current. The format is: Option CT=xxxx where xxxx is the rated current of the CT. See the WattNode for LonWorks – Option CT page for details. The nciCtAmp variablecan be field configured or overridden by the user.
Option PT
This option is available only with the standard WattNode Plus and WattNode Logger models.
Option PT provides support for potential transformers (PTs), making it easier to use the WattNode for LonWorks meters with medium voltage services. Specifically, Option PT adds a configuration property UCPTptRatio which configures the ratio of the external PT, allowing the meter to automatically scale the voltage, power, and energy readings. See WattNode LonWorks – Option PT for more information.
Option B
This option is available only with the standard WattNode for LonWorks meter.
If you need a WattNode meter that behaves like the old WNB series models (model numbers WNB-xx-xxx-FT10), then order a
WNC-xx-xxx-FT10 Opt B
The Option B WattNode models are very similar to the original WNB series WattNode Plus models, but with a few changes:
- New program ID: 8:00022:1500:0A04:05. Because there are some hardware changes, LonMaker® requires a new program ID.
- Energy and time of day are stored to non-volatile memory every 5 seconds. The old version stored these every 20 seconds.
- The energy log has been removed (see our WattNode Logger for LonWorks if you need logging). The nviLogRequest and nvoLogData variables still exist, but do nothing.
- The network variable list is identical to the original WNB series WattNode Plus
- Firmware Version 3.03
Support Information
- WattNode for LonWorks Firmware Versions
- WattNode for LonWorks External Interface Files (xif)
- Support Articles
- Application Notes
Warning: Hazardous Voltages – Only qualified personnel or licensed electricians should install the WattNode meter and current transformers.